(What are Cookies? Privacy) By clicking "accept", you agree to the use of cookies to measure and analyze your interactions with the shop content. You can withdraw your consent at any time.
Filter class according to ISO 16890: ISO Coarse 50% Filter class according to EN 779:2012: G3 Maximum relative humidity: 100 Maximum temperature: 80°C Recommended final pressure drop: 200 Pa Possible nominal volumetric flow (short-time possible): 1.25 x nominal volume flow Fire behaviour: DIN 53438 - 3 (F1)
Technical data:
Filter area [m2]: 1.5 Weight per unit area [g/m2]: 200 Material thickness [mm]: 22.0 Recommended nominal volume flow [m3/h/m2]: 5,400 Face velocity [m/s]: 1.50 Initial pressure difference (measured on a flat sample 610 x 610 mm) [Pa]: 30
Product advantages:
Break-resistant synthetic fibres-100% polyester
Progressive fibre structure-the filter medium is compacted on the clean air side, thus
and thus uses the full depth for dust absorption
Thermally bonded
High dust holding capacity due to the progressive structure of the
media
Testing for paint-wetting impairing substances by the Fraunhofer
IPA
For coarse dust filtration with requirements for higher volume flow rates
and high dust holding capacity
For use in air-conditioning and ventilation equipment and systems, and